Features
- 1-channel system for connecting a max. of 2 pipelines
- Built-in and preconfigured esserbus coupler
- Highly sensitive laser sensors for highest stability
- 9 different adjustable sensitivity levels from 0.07% LD/m
- Programmable pre-alarm levels
- PipeIQ software for intuitive system layout, configuration, and maintenance in a
- simple LED overview with a detailed fault indicator
- Unique airflow pendulum shows the current airflow of the channel
- 10 adjustable fan speeds
- Operating volume from 26 dB(A) (at fan level 1)
- Sophisticated detection algorithms reduce false alarms
- Integrated event memory up to 2244 events
- Ultrasonic flow rate sensor for accurate pipe flow measurement
- USB interface
- IP 65 protection rating
- Removable integrated filter unit
- Operating menu in 24 languages
Approved for the requirements of EN 54-20 classes A, B, and C with the following information:
- Max. 200 m pipeline length per channel
- Max. 20 holes for class C per channel
- Max. 10 holes for class B per channel
- Max. 3 holes for class A per channel
br/>Approved for the requirements of EN 54-20 classes A, B, C using the pre-alarm with the following information:
- Max. 120 m pipeline length per channel
- Max. 12 holes for class C per channel
- Max. 4 holes for class B per channel